15. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50°C
Storage Temperature Range: -40 to 80°C
Operating and Storage Humidity: 85% max. relative humidity
(non-condensing) from 0°C to 50°C.
Altitude: Up to 2000 meters
16. SERIAL COMMUNICATIONS (Optional):
Isolation To Signal Input Common: 500 Vrms for 1 min.
Working Voltage: 50 V max., CAT I
Not isolated from all other commons.
Type: Bi-directional 20 mA current loop, 20 mA source provided on
transmit loop. (Powers up to 7 units in a loop with internal current
source).
Baud Rate: programmable 300 to 2400
Maximum address: 99 (Actual number in a single loop is limited by serial
hardware specifications.)
Data Format: 10 bit frame, Odd parity (one start bit, 7 data bits, one odd
parity bit, and one stop bit.)
Serial Hardware Specifications:
SO - Output Transistor Rating: V
max
= 30 VDC, V
SAT
=1V
max
at 20 mA.
Note: This will allow up to 28 units maximum in each loop.
SI - Input Diode Rating: V
F
= 1.25 V
TYP
; 1.5 V
MAX
Note: The compliance voltage rating of the source must be greater
than the sum of the voltage drops around the loop. (Typically a 30
VDC powered source would be capable of operating between 18
and 22 units in a loop.)
17. ALARMS (Optional):
Solid State: Two, isolated, sinking open collector NPN transistors acting in
parallel with relays. Imax: 100 mA. V
SAT
= 1.0 V @ 100 mA. Vmax: 30 VDC.
Isolation To Signal Input Common: 500 Vrms for 1 min.
Working Voltage: 50 V max., CAT I
Not isolated from all other commons.
Relays:
Isolation To Signal Input Common: 2300 Vrms for 1 min.
Working Voltage: 300 V max., CAT II
Type: Form C (2)
Max. Rating: 5 Amps @ 120/240 VAC or 28 VDC (resistive load), 1/8
hp @ 120 VAC (inductive load).
Relay Life Expectancy: 100,000 cycles at max. rating. (As load level
decreases, life expectancy increases.)
18. ANALOG OUTPUT (Optional): Digital scaling and offsetting
Isolation To Signal Input Common: 500 Vrms for 1 min.
Working Voltage: 50 V max., CAT I
Not isolated from all other commons.
4to20mA:
Accuracy: 0.1% of full scale
Resolution: 12 bits
Compliance Voltage: 10 VDC (500 W max. loop resistance)
0 to 10 VDC:
Accuracy: ±(0.1% of reading + 35 mV)
Resolution: 12 bits
Min. Load Resistance: 10 KW (1 mA max.)
19. PEAK/VALLEY/SLOPE/OFFSET (Optional):
Peak and Valley recording. Programmable temperature offset and slope.